R150N

CATEGORY: WATER MANAGEMENT

Automatic filling unit UseThe R150N valve is a device installed on water intake pipes in closed circuitheating systems and is used for automatic filling and integrated bypass. DescriptionThe R150N valve consists of: a pressure reducer with compensated seatequipped with a filter and check valve, adjustment handwheel (1) for settingdownstream pressure, a manometer (2), an upstream shutoff valve (6) to enablethe emptying of the system through the discharge tap (4), a downstreamshutoff valve (3) t...

Automatic filling unit

Use
The R150N valve is a device installed on water intake pipes in closed circuit
heating systems and is used for automatic filling and integrated bypass.

Description
The R150N valve consists of: a pressure reducer with compensated seat
equipped with a filter and check valve, adjustment handwheel (1) for setting
downstream pressure, a manometer (2), an upstream shutoff valve (6) to enable
the emptying of the system through the discharge tap (4), a downstream
shutoff valve (3) to facilitate the calibration of downstream pressure, and a
stopcock (5) on the bypass pipe integrated into the valve body.
The R150N valve includes a removable cartridge that can be extracted from
the valve body, mounted on the system, by simply closing the upstream and
downstream shutoff valves.
The removable cartridge includes a filter and a check valve

Technical data
- Maximum operating temperature: 70 ºC
- Maximum operating pressure: 10 bar
- Pressure setting: 0,3 ÷ 4 bar
- Factory calibration: 1,5 bar
- Connections: 1/2”F